Kane 457 CPA1 Combustion Analyser Kit

£841.95

£1,010.34

SKU
NEW_CODE261
pricematch
  • Flue Gas & Ambient Air Analyser with Direct CO & CO2 Measurement.
  • Combustion Analysis, Direct CO2 Measurement & Measure CO, CO2 & Ratio.
  • High Accuracy Pressure Measurement, Temperature Measurements & Flow/return, inlet/outlet, hot/cold measurements.
  • CPA1 Kit includes GLD450 gas leak detector, KAL1 air / liquid probe temp probe, pressure hose, 2 x clamp on pipe probes, infra-red printer, rechargeable batteries and carry case.
pdf
(Size: 812.5 KB)
pdf
(Size: 888.7 KB)
More Information
Warranty 6 years
Price Match Yes
Choice of FREE gift

Trade up to KANE!
Experience the latest analysers from Kane at a great price.
Perfect for new and existing engineers!

Kane 457 CPA1 Combustion Analyser Kit

The latest combustion analyser from Kane.

A flue gas analyser, domestic atmosphere analyser (with timed data-logging), differential thermometer and precision pressure meter all in a small, easy to use instrument.

Pro Kit comes complete with GLD450 gas leak detector, KAL1 air / liquid probe temp probe, pressure hose, 2 x clamp on pipe probes, infra-red printer, rechargeable batteries and carry case.

Accurately measures:

  • Carbon dioxide (CO2) in the range 0-20% volume, carbon monoxide (CO), flue and inlet temperature, differential pressure (±80mbar)
  • Oxygen (O2), CO/CO2 ratio, poison index, efficiency(gross, net and condensing)
  • Multi-fuel: Natural gas, light oil (28/35 sec), propane, butane, LPG, wood pellets
  • Long life sensors (expected life up to 5 years)
  • Detachable flue probe
  • Memory stores: 99 combustion tests, 20 pressure and tightness tests, 20 temperature and CO tests

Accurately measures:

  • Carbon dioxide (CO2) in the range 0-9999ppm and carbon monoxide (CO)
  • Timed room CO test
  • Ambient carbon dioxide (CO2) and carbon monoxide (CO) monitoring
  • Timed atmosphere logging (adjustable) with dual CO2 and CO printout (via optional infrared linked thermal printer)

Features:

  • Combustion Analysis - Ideal when installing & commissioning boilers, fires etc
  • Direct CO2 Measurement - Using Infra-red technology for better accuracy
  • Measure CO, CO2 & Ratio - For Benchmark logbook
  • Pressure & Temperature
  • High Accuracy Pressure Measurement - Perform timed let-by, stabilisation & tightness tests
  • Temperature Measurements (with optional probes)
  • Flow/return, inlet/outlet, hot/cold measurements
  • Air Quality
  • Room Ambient Air - Measure and record room CO2 and CO readings for up to 30 minutes
  • Ambient CO2 and CO - Monitor and record real time and maximum CO2 & CO
  • Timed Logging - Establish CO2 & CO concentration profiles over a specific period of time

What's Included?

  • GLD450 gas leak detector
  • KAL1 air / liquid probe temp probe
  • ASP2 appliance sampling probe kit
  • pressure hose
  • 2 x clamp on pipe probes
  • infra-red printer
  • rechargeable batteries
  • 12 charger
  • quick reference DVD
  • carry case

Specifications:

Parameter Range Resolution Accuracy
Flue Temperature 0-600°C 0.1°C ±2.0°C
±0.3% reading
Inlet Temperature 0-50°C 0.1°C ±1.0°C
(Internal Sensor) ±0.3% reading
Inlet Temperature 0-600°C 0.1°C ±1.0°C
(External Sensor) ±0.3% reading
Inlet Temperature 0-600°C 0.1°C ±2.0°C
(External Sensor) ±0.3% reading
Oxygen*2 0-21% 0.10% ±0.3%*1
Carbon monoxide 0-20ppm 1ppm ±0.3%*1
21-2000ppm nom ±3ppm
4,000ppm max for 15 mins ±5% reading
Carbon dioxide 0-20% 0.10% ±0.3% reading
Efficiency (Net or Gross)*2 0-99.9% 0.10% ±1.0% reading
Effeciency High (C)*2 0-119.9% 0.10% ±1.0% reading
Excess Air*2 0-250% 0.10% ±0.2% reading
CO/CO2 ratio *2 0-0.999 0.0001 ±5% reading
Nominal range ±160mBar ±0.2mBar Maximum ±0.005 mBar
Maximum over range without damage to sensor is ±800mBar ±1 mBar 0.001 mBar ±0.03 mBar
  ±160mBar <25 mBar ±3% of reading

 

*1 Using dry gases at STP  
*2 Calculated  
   
Ambient Operating Range Temperature - 0°C to 40°C
Humidity - 10% to 90% RH non-condensing
Atmospheric Pressure - 860 to 1060hPa
Battery Type / Life 4AA cells
>8 hours using Alkaline AA cells
Chargers (optional) 220v charger, for NiMH batteries only
12v in vehicle charger, for NiMH batteries only
Dimensions Weight - 0.8kg handset with protective cover
Handset - 200 x 45 x 90mm
Probe - 300mm long including handle. 6mm diameter x 240mm long stainless steel shaft with 3m neoprene hose. Type K thermocouple